Go to Top

Water Cooled Chiller

The following is a summary of our water cooled chillers specifications:

Model Unit ws101a ws201a ws303a ws403a ws503a
Cooling Capacity* 50 Hz Kcal/hr
60 Hz
6,950
8,340
9,068
10,880
13,600
16,320
16,930
20,310
22,970
27,800
Condenser Air Flow Rate m³/hr 30 40 60 80 100
Chilled Water Pump
Chilled Water Flow Rate
Water Tank Capacity
KW  0.55 0.75
L/min 40/2 Bar  80/3 Bar
L 30 50
Compressor Power Source   200-240V
380-440V 3 PH
(50/60Hz)
Total Running AMPS 10.6
5.6
13.5
7.0
21.0
9.5
27.5
13.6
33.0
16.0
Height mm 1,045 1,045 1,350 1,350 1,505
Width mm 510 510 585 715 715
Depth mm 765 765 1,145 1,145 1,220
Est.Machine Weight KG 100 120 185 220 300
Model Unit ws803a ws1003a ws1503a ws2003a ws3003a
Cooling Capacity* 50 Hz Kcal/hr
60 Hz
33,250
40,230
47,456
57,420
66,500
80,430
94,910
114,840
142,370
170,840
Condenser Air Flow Rate m³/hr 150 220 300 450 650
Chilled Water Pump
Chilled Water Flow Rate
Water Tank Capacity
KW  1.5 3.0 4.0 7.5
L/min 160/3 Bar 250/3 Bar 350/3 Bar 500/3 Bar
L 120 200
300 450
Compressor Power Source   380-440V 3 PH
(50/60Hz)
Total Running AMPS -
25.0
-
33.0
-
52.0
-
69.0
-
100
Height mm 1,555 1,500 1,600 1,930 2,005
Width mm 765 965 995 1,145 1,220
Depth mm 1,475 1,475 1,830 1,830 1,905
Est.Machine Weight KG 450 480 780 950 1,200

*Cooling capacity is based on the following conditions -
Chilled water leaving / entering temperature: 7 / 12°C
Condenser water inlet temperature: 28°C